KYORITSU 4106 Earth Resistance & Resistivity Tester 200kΩ | KEW 4106
Couldn't load pickup availability
The KYORITSU 4106 (KEW 4106) is a digital earth resistance and soil resistivity tester. It measures earth resistance from 0.03Ω to 200kΩ by the fall-of-potential method and calculates soil resistivity by the Wenner 4-pole method, with automatic or manual selection of four test frequencies and FFT noise filtering for stable readings.
Key Features & Benefits
- Wide range: earth resistance 2Ω to 200kΩ ranges with 0.001Ω resolution; resistivity up to 1999kΩ·m.
- Soil resistivity calculated automatically from the spike spacing (1.0–30.0m), Wenner method.
- Four test frequencies (94 / 105 / 111 / 128Hz), auto or manual, to avoid interference.
- FFT noise filtering for stable readings near live systems.
- 800-data memory with PC transfer via the included 8212-USB adapter (KEW Report software).
- IP54 case for field use; auto power-off after approx. 5 minutes.
Technical Specifications
| Function | Range | Accuracy |
|---|---|---|
| Earth resistance 2Ω | 0.03–2.099Ω (0.001Ω resolution) | ±2% rdg ±0.03Ω |
| Earth resistance 20Ω / 200Ω / 2000Ω / 20kΩ / 200kΩ | 0.03Ω to 209.9kΩ (auto-ranging) | ±2% rdg ±5 dgt (auxiliary earth 100Ω, with Rk correction) |
| Auxiliary earth resistance (Rh, Rs) | — | 8% of Re + Rh + Rs |
| Earth resistivity (ρ) | 0.2Ω·m to 1999kΩ·m (auto-ranging); spacing a = 1.0–30.0m | ρ = 2 × π × a × Rg |
| Series interference voltage (Ust) | 0–50.9V AC rms | ±2% rdg ±2 dgt (50/60Hz); ±3% rdg ±2 dgt (40–500Hz) |
| Frequency (Fst) | 40–499.9Hz | ±1% rdg ±2 dgt |
| Test frequency | 94 / 105 / 111 / 128Hz (auto or manual) | — |
| Measuring method | Fall-of-potential (earth resistance); Wenner 4-pole (resistivity) | — |
| Memory | 800 data | — |
| Interface | USB via 8212-USB optical adapter | — |
| Overload protection | AC 280V / 10s (E-S(P) and E-H(C)) | — |
| Power source | DC 12V: R6 (AA) 1.5V × 8 | — |
| Dimensions | 167 (L) × 185 (W) × 89 (D) mm | — |
| Weight | Approx. 900g (including batteries) | — |
Note: the earth voltage function is not designed to measure mains line voltage.
Safety & Compliance
- IEC 61010-1 CAT III 300V / CAT IV 150V, pollution degree 2
- IEC 61010-031
- IEC 61557-1, -5
- IEC 61326-1 (EMC)
- IEC 60529 IP54
What's in the Box
- 7229A earth precision measurement test leads
- 7238A simplified measurement test leads
- 8032 auxiliary earth spikes (2 sets, 4 spikes)
- 8200-04 cord reels (4 pcs)
- 8212-USB USB adapter
- 8923 fuse (0.5A/600V) × 1 fitted + 1 spare
- 9121 shoulder strap and 9125 carrying case
- R6 (AA) batteries × 8 and instruction manual
Applications
- Soil resistivity surveys for earthing system design
- Earth electrode resistance testing for substations, buildings and towers
- Lightning protection system earth checks
| Warranty period | 1 Year Warranty |
|---|---|
| Coverage | Free repair or replacement for defects in material and workmanship arising during normal use within 1 year from the date of purchase. Test leads, probes and plug leads supplied with the instrument are covered for 1 year against production defects. |
| Not covered | Fuses and batteries; normal wear of test leads and probes (cuts, burns, broken tips, worn insulation); damage from accident, dropping, overload, misuse, or use outside the instrument's rated specifications. |
| Warranty void if | The instrument has been opened, repaired or modified by a party not authorised by Kyoritsu or its Malaysian distributor. |
Contact Techno Tools with your proof of purchase (invoice or receipt).
Order by 4PM to get delivered next working day! We use 24 hours service with carriers in most cases so that you can get your order delivered on time.
Free delivery for orders above RM500 with a total weight under 22kg. Otherwise, delivery charges are calculated at checkout based on your order’s weight and delivery location.
Further details please click here for more info.
Please notify us within 14 calendar days of receiving your product to request a free exchange or full refund, if eligible. We will cover all return shipping costs, and no restocking fees will apply in this case.
Requests made after 14 days may be accepted at our discretion and will be subject to a 10% restocking fee. Techno Tools & Equipment reserves the right to reject any return request found to be ineligible.
Further details please click here for more info.