KYORITSU 4200 Earth Clamp Tester (KEW 4200)
Couldn't load pickup availability
Got questions?
Feel free to WhatsApp us
Product Brochure
Click Here: Brochure in PDF
Product Datasheet / User Manual
Click Here: Datasheet in PDF
Model: KEW4200
Shipping Weight: 2.6 kg
Manufacturer: KYORITSU
✅ The earth resistance can be measured from 0.05 to 1200Ω without auxiliary earth spikes. (Applicable for Multiple Earthing Systems.)
✅ True RMS provides accurate readings of AC current, including distorted waveforms from 1mA to 30.0A.
✅ Noise Check Function detects currents affecting earth resistance measurements and displays a "NOISE" indicator on the LCD.
✅ Memory function stores and displays up to 100 measurement data.
✅ Data hold function, buzzer function, and backlight function are included.
✅ Complies with IEC 61010-1 Safety Standards: CAT.IV 300V Pollution degree2.
Note:
Single earthing cannot be measured. (Only applicable for Multiple Earthing Systems)
🌐 Earth Resistance Auto Range
▶ Range: 20Ω
- Resolution: 0.01Ω*
- Measuring range: 0.00~20.99Ω
- Accuracy: ±1.5%±0.05Ω
▶ Range: 200Ω
- Resolution: 0.1Ω
- Measuring range: 16.0~99.9Ω / 100.0~209.9Ω
- Accuracy: ±2%±0.5Ω / ±3%±2Ω
▶ Range: 1200Ω
- Resolution: 1Ω
- Measuring range: 160~399Ω / 400~599Ω
- Accuracy: ±5%±5Ω / ±10%±10Ω
▶ Range: 1200Ω
- Resolution: 10Ω
- Measuring range: 600~1260Ω
- Accuracy: ---
🌐 AC Current (50Hz / 60Hz) Auto Range
▶ Range: 100mA
- Resolution: 0.1mA
- Measuring range: 0.0~104.9mA
- Accuracy: ±2%±0.7mA
▶ Range: 1000mA
- Resolution: 1mA
- Measuring range: 80~1049mA
- Accuracy: ±2%
▶ Range: 10A
- Resolution: 0.01A
- Measuring range: 0.80~10.49A
- Accuracy: ±2%
▶ Range: 30A
- Resolution: 0.1A
- Measuring range: 8.0~31.5A
- Accuracy: ±2%
🌐 Operating System:
▶ Earth Resistance Function:
- Constant voltage injection,
- Current detection,
(Frequency : Approx.2400Hz)
Dual Integration
▶ AC Current Function:
Successive Approximation
🌐 Over-range Indication:
"OL" is displayed when the input exceeds the upper limit of a measuring range.
🌐 Response Time:
Approx.7 seconds for Earth resistance.
Approx.2 seconds for AC current.
🌐 Sample Rate:
Approximately once per second.
🌐 Power Source:
D (Details not provided)