Fluke FK FEV300/TY1 & TY2 EV Charging Station Test Adapter Kit: Type 1 & 2 Connectors
Couldn't load pickup availability
Got questions?
Feel free to WhatsApp us
Product Brochure
Click Here: Brochure in PDF
Product Datasheet / User Manual
Click Here: Datasheet in PDF
Fluke FEV300 EV Charging Station Test Adapter Kit: Type 1 & 2 Connectors
The FEV300 test adapter kit with Type 1 and Type 2 connectors is designed to test function and safety of charging stations mode 3 for AC charging. The adapter imitates an electric vehicle and opens up a charging cycle, activating voltage and current output, allowing you to conduct tests in combination with appropriate test instruments like an installation tester (Fluke 1664 FC) and/or a ScopeMeter® (Fluke 120B Series). With the adapter kit, charging stations can be tested in accordance with IEC/EN 61851-1 and IEC/HD 60364-7-722.
Proximity Pilot (PP) state “Cable Simulation”: With PP State rotary switch the adapter can simulate various current capabilities of charging cables
Control Pilot (CP) state “Vehicle Simulation”: With CP State rotary switch selector various charging states can be simulated
Simulation of CP error “E”, simulation of PE error (Earth fault)
Simplicity and convenience
Perform a variety of tests including ground fault checks, insulation of wires, measuring voltage and duty cycle to see max current available for charging all in one adapter that safely integrates with the Fluke portfolio of test and measurement tools. The FEV300 allows you to simulate CP (E) and PE (Earth Fault) error and includes separate phase indication by three LED lamps for easy check if voltage is present. There is no need to bring an electric vehicle onsite for charging station troubleshooting: the adapter acts as an electric vehicle when connected to a charging station for easy performance and maintenance testing.
What's in the box:
FEV300/BASIC Test Adapter
FEV300-CON-TY1 Type 1 Plug
FEV300-CON-TY2 Type 2 Plug
Carrying case (FLUKE C120B)
Features:
Input voltage: Up to 250 V (single phase system) / up to 480 V (three phase system), 50/60 Hz, max 10 A
Internal power consumption: 3 W max.
FEV300-CON-TY2 Plug: AC charging mode 3, suitable to IEC 62196-2 type 2 socket outlet or fixed cable with vehicle connector (type 2, 7P three-phase)
FEV300-CON-TY1 Plug: AC charging mode 3, suitable to IEC 62196-2 type 1 or SAE J1772 with vehicle connector (type 1, 5P single-phase)
Dimensions (H × W × D): 110 × 45 × 220 mm length without connection cable and test cable
Weight (including type 1 or type 2 connection cable): 1 kg
Safety standards: IEC/EN 61010-1, pollution degree 2, IEC/EN 61010-2-030, CAT II 300 V, protection class II
Ingress protection: IEC 60529: IP54 (housing), IEC 60529: IP54 (sockets with protection caps in place, connectors in connected condition or with protection caps in place, otherwise IP20)
Operating temperature: -20 °C to 40 °C
Storage temperature: -20 °C to 50 °C
Operating humidity range: 10 % to 85 % relative humidity non-condensing
Storage relative humidity: 0 % to 85 % non-condensing
Operating altitude: 2000 m max.
Functions
PE Pre-Test: Visible indication >50 V AC/DC between PE conductor and touch sensor
PP Simulation: Open, 13 A, 20 A, 32 A, 63 A
CP States: State A, B, C, D
CP Error state “E”: On/off (CP signal short-circuited to PE)
PE Error state "F" (Earth fault): On/off (interruption of PE conductor)
Outputs (for test purpose only)
Measuring terminals L1, L2, L3, N, PE: Max. 250/480 V, max. 10 A
CP signal output terminals: Approx. +/-12 V
Caution: In case of wrong wiring or error of the charging station these terminals may be hazardous.