Click Here: Datasheet in PDF
Bar graph to display insulation resistance
- Bar graph to display insulation resistance
- Displays the value of external AC voltage with flashing symbol
- Auto null function to automatically subtract the test lead resistance before displaying the real continuity resistance value
- Trac-Lok mode to conserve battery life on insulation and continuity tests
- Live circuit warning buzzer
- Releasing the test button automatically discharges the charges stored in the circuit under test
- Backlight function to view the test results in dimly lit areas
- 200mA measuring current on continuity testing
Shipping Weight: 1.4 kg
Manufacturer: KYORITSU
- Bargraph displays insulation resistance.
- Shows external AC voltage value with a flashing symbol.
- Auto null function automatically subtracts test lead resistance before displaying actual continuity resistance value.
- Trac-Lok mode conserves battery life during insulation and continuity tests.
- Live circuit warning beeper.
- Releasing the test button automatically discharges charges stored in the circuit under test.
- Backlight function for viewing test results in dimly lit areas.
- 200mA continuity measuring current meets IEC 61557 standard.
- Minimum 1mA current on insulation tests meets IEC 61557 standard.
Insulation Resistance
- Test Voltage: 250V/500V/1000V
- Measuring Ranges (Mid-scale Value): 20MΩ/200MΩ/2000MΩ
- Output Voltage on open circuit: Rated test voltage +20%, -0%
- Nominal Current: Minimum 1mA DC
- Output Short Circuit Current: Approximately 1.5 mA DC
- Accuracy:
|±1.5% reading ±5 digits (20MΩ/200MΩ)
|±10% reading ±3 digits (2000MΩ)
Continuity Test
- Measuring Ranges (Mid-scale Value): 20Ω/200Ω/2000Ω
- Output Voltage on open circuit: 7~12V DC
- Measuring Current: Minimum 200mA DC
- Accuracy:
|±1.5% reading ±5 digits (20Ω)
|±1.5% reading ±3 digits (200Ω/2000Ω)
AC Voltage
- AC Voltage Range: 0-600V AC
- Accuracy: |±5% reading ±3 digits
General
- Safety Standard:
IEC 61010-1 CAT.III 300V Pollution Degree 2
IEC 61010-2-031
IEC 61557-1/2/4
- IP Rating: IEC 60529-IP54
- EMC Standard: IEC 61326-1
- Withstand Voltage: Withstands up to 3700V AC for one minute
- Power Source: R6P (AA) (1.5V) ×8
- Dimensions:
Length:185 mm
Width:167 mm
Depth:89 mm
Weight:
Approximately:990g
Accessories:
Test leads (7122B), Pouch for test leads, Fuses (8923 F500mA/600V) ×2, Batteries (R6P AA) ×8, Shoulder Strap, Instruction Manual
Country of Origin:
Thailand